CY LSZH Control Cable

  • CY LSZH Control Cable
  • starmile

CY LSZH Control Cable

 

 

 

Application:

Cable Standards:
Low smoke zero halogen CY flexible control cable is used in installations where a screen is required to prevent interference on data and signal transmissions. The flexible cable is also used on measuring as well as checking and control equipment in areas where there is risk to life from fire, smoke emissions and toxic fumes.VDE 0207-303-7,
Flame Retardant according to IEC/EN 60332-1-2,
IEC/EN 60332-3-24
Low Smoke Zero Halogen according to IEC/EN 60754-1/2,
IEC/EN 61034-1/2

Product Description:

ConductorPlain Annealed Flexible Copper
InsulationLow Smoke Zero Halogen (LSZH)
ScreenTinned Copper Wire Braiding
Sheath materialLow Smoke Zero Halogen (LSZH)

Characteristics:

Voltage Rating Uo/U300/500V
Temperature RatingFixed: -40°C to +80°C
Flexed: -15°C to +70°C
Minimum Bending RadiusFixed: 6 x overall diameter
Flexed: 15 x overall diameter

Core Identification:

3 Core and aboveBlack withWhite numbers
Numbers plusGreen/Yellow

Also available with coloured cores as follows:

3 Core:BlueBrownGreen/Yellow
4 Core:BrownBlackGreyGreen/Yellow
Should not be installed at temperatures below -5

Dimensions:

Zion CodeNo. Of
Cores
Conductor Size (mm2)Stranding (mm)Weight (kg/km)Outside Diameter (mm)Gland Size (mm)
CY02075O20.7524/0.2043.05.520/16
CY03075O30.7524/0.2052.05.820/16
CY04075O40.7524/0.2068.06.520/16
CY05075O50.7524/0.2080.07.120/16
CY07075O70.7524/0.2103.07.620/16
CY0215O21.5030/0.2561.06.520/16
CY0315O31.5030/0.2578.06.920/16
CY0415O41.5030/0.25104.07.720/16
CY0515O51.5030/0.25128.08.620/16
CY1215O121.5030/0.25281.012.725.0
CY1815O181.5030/0.25396.014.725.0
CY2515O251.5030/0.25534.017.525.0
CY3415O341.5030/0.25720.019.932.0
CY0225O22.5050/0.25102.08.020/16
CY0325O32.5050/0.25117.08.420/16
CY0425O42.5050/0.25168.09.220S
CY0440O44.0056/0.25239.011.820S
CY0460O46.0084/0.30327.012.920S
CY0560O56.0084/0.30543.016.725.0
CY04100O410.0080/0.40553.017.225.0
CY04160O416.00126/0.40846.021.032.0
Note: CY: Means Type; 0275 Means 2 Core, 0.75mm2; O= LSZH

Conductor Resistance:

Nominal Cross Sectional Area (mm2)Maximum Diameter Of
Wires In Conductor mm
Maximum Resistance Conductor
At 20
Plain Wires Ohms/km
0.509.039.00
0.7512.026.00
1.0015.019.50
1.5018.013.30
2.5026.07.98
4.0034.04.95
6.0044.03.30
10.0061.01.91
16.0082.01.21

Current Capacity:

Nominal Cross Sectional Area (mm2)Current Carry Capacity
At 30 In Air Amps
Current Carry Capacity At 30
In Conduit (amps)
0.7516.09.00
1.0020.012.00
1.5024.015.00
2.5032.018.00
4.0042.026.00
6.0054.034.00
10.0073.044.00
16.0098.061.00

Voltage Drop:

Nominal Cross Sectional Area (mm2)Two Core Cable Dc
Mv/a/m
Single Phase Two Core Cable Ac
Mv/a/m
Three Phase 3 Or 4 Core Cable Ac
Mv/a/m
1.0044.044.038.0
1.5029.029.025.0
2.5018.018.015.0
4.0011.011.09.5
6.007.37.36.4
10.004.44.43.8
16.002.82.82.4